Optigo Networks ONS NC600

View CSAF

1. EXECUTIVE SUMMARY

  • CVSS v4 9.3
  • ATTENTION: Exploitable remotely/low attack complexity
  • Vendor: Optigo Networks
  • Equipment: ONS NC600
  • Vulnerability: Use of Hard-coded Credentials

2. RISK EVALUATION

Successful exploitation of this vulnerability could allow an attacker to establish an authenticated connection with the hard-coded credentials and perform OS command executions.

3. TECHNICAL DETAILS

3.1 AFFECTED PRODUCTS

The following versions of Optigo Networks ONS NC600 are affected:

  • ONS NC600: Versions 4.2.1-084 through 4.7.2-330

3.2 VULNERABILITY OVERVIEW

3.2.1 USE OF HARD-CODED CREDENTIALS CWE-798

In Optigo Networks ONS NC600 versions 4.2.1-084 through 4.7.2-330, an attacker could connect with the device's ssh server and utilize the system's components to perform OS command executions.

Unsophisticated Cyber Actor(s) Targeting Operational Technology

CISA is increasingly aware of unsophisticated cyber actor(s) targeting ICS/SCADA systems within U.S. critical Infrastructure sectors (Oil and Natural Gas), specifically in Energy and Transportation Systems. Although these activities often include basic and elementary intrusion techniques, the presence of poor cyber hygiene and exposed assets can escalate these threats, leading to significant consequences such as defacement, configuration changes, operational disruptions and, in severe cases, physical damage. CISA strongly urges Critical Infrastructure Asset Owners and Operators to review the following fact sheet for detailed guidance on reducing the risk of potential intrusions:

CISA Adds Two Known Exploited Vulnerabilities to Catalog

CISA has added two new vulnerabilities to its Known Exploited Vulnerabilities Catalog, based on evidence of active exploitation.

  • CVE-2025-34028 Commvault Command Center Path Traversal Vulnerability
  • CVE-2024-58136 Yiiframework Yii Improper Protection of Alternate Path Vulnerability

These types of vulnerabilities are frequent attack vectors for malicious cyber actors and pose significant risks to the federal enterprise.

CISA Adds Two Known Exploited Vulnerabilities to Catalog

CISA has added two new vulnerabilities to its Known Exploited Vulnerabilities Catalog, based on evidence of active exploitation.

  • CVE-2024-38475 Apache HTTP Server Improper Escaping of Output Vulnerability
  • CVE-2023-44221 SonicWall SMA100 Appliances OS Command Injection Vulnerability

These types of vulnerabilities are frequent attack vectors for malicious cyber actors and pose significant risks to the federal enterprise.

KUNBUS GmbH Revolution Pi

View CSAF

1. EXECUTIVE SUMMARY

  • CVSS v4 9.3
  • ATTENTION: Exploitable remotely/low attack complexity
  • Vendor: KUNBUS
  • Equipment: Revolution Pi
  • Vulnerabilities: Missing Authentication for Critical Function, Authentication Bypass by Primary Weakness, Improper Neutralization of Server-Side Includes (SSI) Within a Web Page

2. RISK EVALUATION

Successful exploitation of these vulnerabilities could allow attackers to bypass authentication, gain unauthorized access to critical functions, and execute malicious server-side includes (SSI) within a web page.

3. TECHNICAL DETAILS

3.1 AFFECTED PRODUCTS

The following versions of KUNBUS Revolution Pi are affected:

MicroDicom DICOM Viewer

View CSAF

1. EXECUTIVE SUMMARY

  • CVSS v4 8.6
  • ATTENTION: Exploitable remotely/low attack complexity
  • Vendor: MicroDicom
  • Equipment: DICOM Viewer
  • Vulnerabilities: Out-of-Bounds Write, Out-of-Bounds Read

2. RISK EVALUATION

Successful exploitation of these vulnerabilities could allow an attacker to disclose information, cause memory corruption, and execute arbitrary code.

3. TECHNICAL DETAILS

3.1 AFFECTED PRODUCTS

The following MicroDicom products are affected:

  • DICOM Viewer: Versions 2025.1 (Build 3321) and prior

3.2 VULNERABILITY OVERVIEW

3.2.1 OUT-OF-BOUNDS WRITE CWE-787

MicroDicom DICOM Viewer is vulnerable to an out-of-bounds write which may allow an attacker to execute arbitrary code. The user must open a malicious DCM file for exploitation.

CISA Releases Three Industrial Control Systems Advisories

CISA released three Industrial Control Systems (ICS) advisories on April 29, 2025. These advisories provide timely information about current security issues, vulnerabilities, and exploits surrounding ICS.

CISA encourages users and administrators to review newly released ICS advisories for technical details and mitigations.